Electrician (ELE)

Fourth Period Package (41 Modules) Comments

Date: 10/17/2022 10:17:13 AM
Module: 030401a
Version: 24
Page: 11
Comment: Both calculations at the bottom of the page say "Use Ohm's Law to calculate impedance..." but are actually calculating current. Change "impedance" to "current" in both situations.
Status: Implemented

Date: 8/28/2023 2:19:27 PM
Module: 030401a
Version: 24
Page: 19
Comment: DC voltage ratings. The typical voltage ratings for DC motors and Generators are listed, but should the list have "or" in it rather than "and" IE The typical voltage ratings are 125, 250, or 500 VDC for generators and 90,120,180,240, 500, or 550 VDC for DC motors. There has been some feedback that the way they are written leads the reader to believe a single machine could have multiple voltage ratings. It could also be changed to: The typical maximum voltage ratings are 125, 250, or 500 VDC for generators and 90, 120, 180, 240, 500, or 550 VDC for DC motors. DC motors deliver rated torque and rated speed at rated voltage but can operate at reduced voltage indefinitely at reduced load without harm so the voltages are really maximums.
Status: Approved for Review

Date: 8/29/2023 3:15:35 PM
Module: 030401a
Version: 24
Page: 30
Comment: The phasor diagram for the Wye voltages has an error V bn is drawn at 240 degrees which is correct but labeled 270 degrees.
Status: Approved for Review

Date: 10/2/2023 3:28:56 PM
Module: 030401a
Version: 25
Page: 12
Comment: The text in the last line of the last paragraph has "resistance" written twice
Status: Approved for Review

Date: 8/28/2023 2:07:04 PM
Module: 030401b
Version: 24
Page: 18
Comment: Under temperature rise the second paragraph starts out with: "The ambient temperature is the temperature of the cooling medium." This is misleading, the ambient temperature is, by definition, the temperature of the surrounding atmosphere. The cooling medium will also be at that temperature before the machine starts producing any heat, which is where I believe the statement was aiming. I suggest: "The ambient temperature is the temperature of the cooling medium before any heating or cooling effect is imparted from the machine." OR "The ambient temperature is the temperature of the atmosphere around the machine and this will also be the temperature of the cooling medium before the machine begins to produce heat."
Status: Approved for Review

Date: 8/29/2023 3:25:42 PM
Module: 030401b
Version: 24
Page: 19
Comment: Comment: DC voltage ratings. The typical voltage ratings for DC motors and Generators are listed, but should the list have "or" in it rather than "and" IE The typical voltage ratings are 125, 250, or 500 VDC for generators and 90,120,180,240, 500, or 550 VDC for DC motors. There has been some feedback that the way they are written leads the reader to believe a single machine could have multiple voltage ratings. It could also be changed to: The typical maximum voltage ratings are 125, 250, or 500 VDC for generators and 90, 120, 180, 240, 500, or 550 VDC for DC motors. DC motors deliver rated torque and rated speed at rated voltage but can operate at reduced voltage indefinitely at reduced load without harm so the voltages are really maximums. I put the wrong ILM number on this before
Status: Approved for Review

Date: 10/17/2022 10:21:59 AM
Module: 030401d
Version: 24
Page: 35
Comment: Question 11 in the Objective Two Exercise needs to say "...lagging power factor angle..." to make the answer in the back of the module correct. Higher power factor loads (e.g., resistors) have lower %Vreg, while higher power factor ANGLE loads (e.g., coils) have higher %Vreg. Add "angle" to the question stem OR change the answer to "a) decrease".
Status: Implemented

Date: 2/24/2020 7:44:14 AM
Module: 030401e
Version: 21
Page: 14
Comment: The first bullet point at the top pf page 14 that states the value of current is determined by the resultant voltage (Eresultant) is fundamentally incorrect as well as the formula at the bottom of figure 9 on that same page. This machine at the end of the day is still just a motor and has to follow the principles of Kirchhoffs voltage law. What the modules refers to as Vphase is the applied voltage from the source therefore the voltages Eresultant + Egenerated = Vphase. This is stated in every textbook that describes synchronous motors. This ILM is the only reference that ever makes this statement and that is because it is wrong. This also make all of the phasor diagrams that follow incorrect. The generated voltage will lag Vpahse by the torque angle which will again prove KVL and also aline with every other text out there.
Status: Update in Progress

Date: 10/17/2022 10:24:08 AM
Module: 030401e
Version: 24
Page: 17
Comment: The fourth paragraph says "Use Ohm's Law to solve for impedance..." but is actually calculating armature current. Change "impedance" to "armature current".
Status: Implemented

Date: 10/23/2023 11:57:20 AM
Module: 030401e
Version: 25
Page: 4
Comment: The second paragraph doesn't make sense, as it says that the rotor of a synchronous motor is different from a rotating field alternator (or induction motor) because the rotor supports the field windings, but a rotating field alternator also has field windings installed on the rotor. The statement is true comparing a synchronous motor rotor to an induction motor, but false when comparing a syncronous motor to a rotating field alternator. In addition the amortisseur windings in a synchronous motor are the same as the dampening windings in an alternator. so this is not a difference either.
Status: Approved for Review

Date: 10/17/2022 10:30:53 AM
Module: 030401f
Version: 24
Page: 10
Comment: The last paragraph at the bottom of the page says to reverse the motor by "...interchanging the start-winding leads." However, this should be the "auxiliary winding" in a two-value capacitor motor (as per Figure 5 above the paragraph). Change "start-winding" to "auxiliary winding".
Status: Implemented

Date: 11/3/2023 9:48:04 AM
Module: 030401f
Version: 25
Page: 2
Comment: The ILM states that the most common single phase motors are between 1/6 to 3/4 hp. This is seems much more like an opinion than a fact. For students who work primarily in rural areas, agricultural and small commercial operations single phase motors up to 7.5 hp are very common especially in grain operations using aeration and or milling equipment. I agree that in applications where motors of 1 hp or larger are needed three phase motors are preferred, but due to the number of people who have large air compressors, table saws, and other such equipment as mentioned before in their residential garages, or farms the number of these larger single phase motors being used is quite substantial.
Status: Approved for Review

Date: 1/8/2021 3:14:19 PM
Module: 030402d
Version: 21
Page: 27
Comment: Grounding control transformers references 10-206 subrule (2) for an exception for systems that use less than 1000VA. This is no longer the correct rule, and I do believe with the 2018 update also no longer true. I also believe there is a typo in the first sentence and it meant to read mutual induction transformers.
Status: Implemented

Date: 5/8/2023 2:36:43 PM
Module: 030402e
Version: 24
Page: 20-23
Comment: Figures 15-19 are supposed to show the circuit from Figure 14 programmed in the five different languages, however there are several errors throughout. First, Figure 15 establishes the addresses for the stop (addr 0), start (addr 1), holding contacts (addr 2), overload contacts (addr 3), coil (addr 30), and lamp (addr 31). However in Figures 16-19, the addresses for the holding contacts and overload contacts have been reversed. Second, In Figures 16-19, the coil address is changed from 30 to 0 and the lamp is dropped completely from the diagrams. Third, the overload contacts are completely missing from the instruction list in Figure 19. My suggested fix would be to correct all diagrams to align the addresses, and to just remove the lamp from Figures 14 and 15.
Status: Implemented

Date: 12/8/2022 10:52:52 AM
Module: 030403a
Version: 24
Page: 38
Comment: Wrong number on ULC standard. Module says ULC-s535-M. Correct Standard is ULC-S553-M.
Status: Implemented

Date: 10/31/2023 12:04:09 PM
Module: 030403a
Version: 25
Page: 41 and 42
Comment: Question #6 asks what happens when the air pressure in a dry system drops. There are multiple dry systems, but the two main ones are: A pre action system where there is a monitor to check for air pressure, and water is only available when the FA panel goes into alarm. If this system loses air pressure a supervisory signal is annunciated. There are also systems where there is water available at all times, but air pressure holds the water back (used in sections of a fire alarm system where part of the piping is subject to freezing. In this system the drop in pressure would allow water to flow and therefore cause an alarm. The answer given is that a supervisory condition would occur. However both answers could be true depending on the design of the system. Question #10 is also incorrect as smoke alarms should be mounted on the ceiling or as close to the ceiling as possible, and they must be interconnected within a dwelling unit. Mounted on the wall when possible should not be given as the correct answer.
Status: Approved for Review

Date: 10/21/2022 11:44:11 AM
Module: 030403e
Version: 24
Page: 29
Comment: The diamond block at the top of Figure 7 should say "Is the electrical equipment operating at more than 30 V ac or 60 V dc?"
Status: Implemented

Date: 12/5/2022 9:41:51 AM
Module: 030403e
Version: 24
Page: 20
Comment: It looks like the values from Figure 3 got copy-and-pasted into Figure 6 when these figures were updated. The "Incident Energy" in Figure 6 should be "98 cal/cm". The "Arc Flash Boundary" in Figure 6 should be "25 feet".
Status: Implemented

Date: 2/7/2023 9:18:27 AM
Module: 030403e
Version: 24
Page: 4
Comment: The second bullet point at the top of page 4 should say "Performing..."
Status: Implemented

Date: 12/5/2022 9:46:10 AM
Module: 030403e
Version: 24
Page:
Comment: All of the references to "cal/cm" in Figures 3, 4, 5, and 6 (5 instances) should be "cal/cm2" (with the 2 superscript). The unit of measurement is cal per centimetre squared.
Status: Implemented

Date: 10/17/2022 1:00:07 PM
Module: 030403e
Version: 24
Page: 19
Comment: There seems to be a sentence missing from the top of page 19, there are only figure #s left. Replace "Figure6Figure3" with "When an incident energy analysis has been completed for a power system that you have to work on, you will see detailed arc flash and shock warning labels on the electrical equipment, such as those shown in Figure 3, Figure 4, Figure 5 and Figure 6.
Status: Implemented

Date: 10/17/2022 11:54:03 AM
Module: 030403e
Version: 24
Page: 15
Comment: Fix formatting error in the last paragraph that is displaying "Error! Reference source not found".
Status: Implemented

Date: 10/17/2022 10:38:57 AM
Module: 030403f
Version: 24
Page: 5
Comment: The pie chart in Figure 4 is outdated. There are no longer 6 blocks and the percentages are incorrect. Replace Figure 4 with the current information from the Construction Electrician RSOS.
Status: Implemented

Date: 10/17/2022 10:36:58 AM
Module: 030403f
Version: 24
Page:
Comment: All references to the "National Occupational Analysis (NOA)" need to be changed to the "Red Seal Occupational Standard (RSOS)". It hasn't been called the NOA in years.
Status: Implemented

Date: 9/9/2022 7:48:54 PM
Module: 030405a
Version: 24
Page: 3
Comment: The third paragraph under Conductor Allowable Ampacities refers to 12-204 and 12-212 and Table 20. Rule 12-212 and Table 20 have both been deleted.
Status: Implemented

Date: 10/17/2022 10:41:38 AM
Module: 030405a
Version: 24
Page: 13
Comment: The grammar in the first sentence of Question 2 in the Objective One Activity doesn't make sense. Change to "Three three-wire, single-phase branch circuits are run in a conduit."
Status: Implemented

Date: 10/2/2023 3:17:53 PM
Module: 030405a
Version: 25
Page: 31
Comment: Question 7 is incorrect, In order to get the correct answer to the question you apply a 70% de rating factor for sheath currents to the conductor ampacity as if they were installed in free air as per rule 4-008. However in Appendix B it states that the correction factor for direct buried cables must be obtained from the cable manufacturer as it may be more favorable than 70%. Change the question so that we have eliminated the sheath currents like we do in the real world and use the value from table D9A, or make them free air and use table 1 and apply the 70%
Status: Approved for Review

Date: 10/17/2022 10:42:57 AM
Module: 030405b
Version: 24
Page: 21
Comment: Change "10-614" to "10-616" in Figure 18.
Status: Implemented

Date: 11/23/2023 10:05:28 AM
Module: 030405b
Version: 25
Page: 5
Comment: Figure 6 shows the system bonding jumper connected in the consumer portion of the combination panelboard. The connection of the system bonding jumper should be shown in the service box portion.
Status: Approved for Review

Date: 1/27/2023 12:26:47 PM
Module: 030405c
Version: 24
Page: 30
Comment: Typo on page 30. Change “Table 9G” to “Table 9E” in Step 6.
Status: Implemented

Date: 1/27/2023 12:35:54 PM
Module: 030405c
Version: 24
Page: 56
Comment: Change "600 V" to "1000 V" in Self-Test question 2. Table D1 in the CE Code indicates that RWU insulation has 1000 V ratings only.
Status: Implemented

Date: 2/3/2023 12:21:29 PM
Module: 030405c
Version: 24
Page: 59
Comment: The answer to Question 2 of the Objective Six Activity should be "267 mm", not "330 mm".
Status: Implemented

Date: 10/17/2023 9:57:10 AM
Module: 030405c
Version: 25
Page: 15
Comment: In the ILM it states that the hinges on a splitter should be at the bottom so that the door does not fall on the electricians hands. There is no code that states this. The code rule quoted only states that the label must be legible, and even if that does mean right side up, I investigated some splitters in stock at EECOL in Red Deer and found that of the splitters in stock (we looked at 6 of them) 4 had the label affixed to be right side up with the hinges at the top and 2 had the label affixed so that the hinge was at the bottom. In my personal experience I have heard arguments that the ILM is correct, but in the city of Red Deer, inspectors always wanted the hinges at the top so that if the latch to the splitter is accidentally unhooked gravity will force the door closed rather than open. The information shown in the ILM is therefore opinion not law and should not be included in the curriculum.
Status: Approved for Review

Date: 10/17/2022 10:44:33 AM
Module: 030405d
Version: 24
Page: 10
Comment: Delete the reference to "100 A" OR change it to "1000 A". Ground fault protection equipment is not required in 100 A circuits. Figure 6.
Status: Implemented

Date: 10/17/2022 10:46:27 AM
Module: 030405d
Version: 24
Page: 11
Comment: The neutral conductor supplying the ground fault protection equipment (from the left-hand side) is missing from Figure 6. Add a line to represent the neutral conductor.
Status: Implemented

Date: 11/15/2022 12:51:05 PM
Module: 030405e
Version: 24
Page: 5
Comment: The description of calculating lumens and the associated formula are incorrect. Change “…one lumen times 4π…” in the second line of the first paragraph to “…one candela times 4π…”. Change formula above Figure 2 to “1 cd x 4π x 1 m = 12.57 lm”.
Status: Implemented

Date: 11/29/2022 11:39:26 AM
Module: 030405f
Version: 24
Page:
Comment: The ANSI/TIA-568 standard changed from version C to D in 2015. There are THREE places to make this update in 030405f. Change “ANSI/TIA 568-C.2” in the third paragraph page 5 to “ANSI/TIA-568-D”. Change “ANSI/TIA-568-C” in the first paragraph of page 27 to “ANSI/TIA-568-D”. Change “ANSI/TIA 568-C” in the Objective Two Activity Answers in page 40 to “ANSI/TIA-568-D”.
Status: Implemented

Date: 11/29/2022 11:43:42 AM
Module: 030405f
Version: 24
Page: 1
Comment: Add "ANSI/TIA-568-D Telecommunications Cabling Standard" to the "Resources"
Status: Implemented

Date: 11/29/2022 11:51:31 AM
Module: 030405f
Version: 24
Page: 12
Comment: In the last paragraph, the information about the new terminology is outdated now that the 568 standard is in the "D" version. Reword as follows: “A common terminology has evolved from the ANSI/TIA-568 Standard. Some of terminology changed between the 568-B and 568-C versions of the standard. Distributor, Cable Subsystem 1, and Cable Subsystem 2 are new terms adopted in the C version, and are explained below. The previously used terms are still common in industry, and are shown in brackets following the new terms.”
Status: Implemented

Date: 11/29/2022 11:53:24 AM
Module: 030405f
Version: 24
Page: 14
Comment: Reword the second paragraph as follows: “Figure 12 is an example of a typical building cabling infrastructure. The previously used terminology is in brackets.”
Status: Implemented

Date: 10/17/2022 11:59:58 AM
Module: 030405f
Version: 24
Page: 34
Comment: The "crossed pairs" example in Figure 29 is showing both crossed pairs and reversed pairs (crossed since 3 and 6 are in the wrong place, reversed since the tip and ring conductors are swapped). The simplest fix for this is to replace the "3" and "6" with "4" and "5". OR it can be fixed by swapping the solid and dashed lines and leaving the 3 and 6 as is.
Status: Implemented

Date: 10/31/2022 9:22:59 AM
Module: 030405g
Version: 24
Page: 29
Comment: Objective 4, Figure 8 – The wall space to the right of the range should be marked with a distance since it is usable as per 26-722 d) iii). This error has been carried through this ILM since the 2012 version the codebook when the wording changed from "behind" to "along".
Status: Implemented

Date: 10/31/2022 9:26:34 AM
Module: 030405g
Version: 24
Page: 29
Comment: Objective 4, Figure 8 – The wall space in the dining area requires measurements and additional receptacles as per 26-722 d) vi). This error has been carried through this ILM since the 2015 version of the Codebook.
Status: Implemented

Date: 10/31/2022 9:17:56 AM
Module: 030405g
Version: 24
Page: 43
Comment: The answer key for the Objective 2 Activity was not updated for the 2021 Codebook. The answer to Q.2 should read “Four spaces; refer to Rule 8-108 1)”.
Status: Implemented

Date: 11/23/2023 11:08:56 AM
Module: 030405g
Version: 25
Page: 9
Comment: Last paragraph should state "Rule 8-200 (1b) is 14400 W not 14000W
Status: Approved for Review

Date: 2/3/2023 12:00:42 PM
Module: 030405h
Version: 24
Page: 30
Comment: There is a typo in Figure 5 on page 30. The rule reference on the right-hand side of the figure should be "10-210 d)".
Status: Approved for Review

Date: 2/5/2024 9:52:21 AM
Module: 030405h
Version: 25
Page: 17
Comment: When adding the parking lot receptacles into the main service ampacity calculation the reason that rule 8-202, 3) b) does not apply to the calculated value of the parking receptacles is due to the Standata which is of course only applicable in Alberta. Rather than the statement "Remember that no further demand factor is allowed for the parking lot receptacles" it should be stated that this is because of the Standata. Especially for students who will be writing the Interprovincial Exam there needs to be justification for the statement.
Status: Approved for Review

Date: 11/28/2022 12:59:08 PM
Module: 030405j
Version: 24
Page: 54
Comment: The answer given for Q.7 is the correct answer for Q.6. Delete the current answer for Q.6 and copy and paste the answer for Q.7 into that space. Then make the answer for Q.7 "a) True; Rule 26-244 1)".
Status: Approved for Review

Date: 11/30/2022 8:41:39 AM
Module: 030405j
Version: 2.4
Page:
Comment: 26-256(4) We are avoiding questions using this rule. We should have 2 examples to verify that student is receiving this information.
Status: Approved for Review

Date: 11/9/2022 2:43:17 PM
Module: 030405k
Version: 24
Page:
Comment: The correct answer for question 4 in the Self-Test is a 225 A overcurrent device. Change option a) to 225 A and adjust the answer key to match. The correct math as per the ILM is as follows: 30 A x 0.63 = 18.9 -- #14<20A> -- 40 A vs 60 A, pick 40 Ao/c 55 A x 0.89 = 48.95 -- #8<50A> -- 100 A vs 110 A, pick 100 Ao/c 26 A x 1 = 26 -- #10<35A> -- 70 A vs 52 A, pick 50 Ao/c 82 A x 0.95 = 77.9 -- #4<85A> -- 170 A vs 164 A, pick 150 Ao/c 150 Ao/c is the largest, therefore: Feeder o/c = 150 Ao/c + 48.95 A + (26 A x 0.85) + (18.9 A x 0.7) = 234.2 A – 225 Ao/c
Status: Implemented

Date: 10/17/2022 12:02:17 PM
Module: 030405k
Version: 24
Page: 22
Comment: The correct answer for Question 5 in the Self-Test should be "c) L6-60R".
Status: Implemented

Date: 11/28/2022 12:53:07 PM
Module: 030405l
Version: 24
Page: 17
Comment: Delete the last paragraph of the page. Rule 18-150 2) c) no longer has this requirement.
Status: Approved for Review

Date: 11/22/2022 11:45:14 AM
Module: 030405l
Version: 24
Page: 40
Comment: For question 3 in the Self-Test, both " b) Petroleum Naphtha" and "c) Isoprene" are correct answers (IIA gasses below 300 degrees). Change "c) Isoprene" to "c) Diethyl Ether", which is incorrect because it is a IIB gas.
Status: Implemented

Date: 10/17/2022 12:05:42 PM
Module: 030405l
Version: 24
Page: 36
Comment: Change “these locations” in the NOTE to “corrosive locations”.
Status: Implemented

Date: 10/17/2022 12:03:42 PM
Module: 030405l
Version: 24
Page: 10
Comment: Change “and providing” in the fourth line of the third paragraph to “or providing”.
Status: Implemented

Date: 10/17/2022 12:08:14 PM
Module: 030405l
Version: 24
Page: 43
Comment: For questions 5 & 6 in the Objective Two Activity Answers, delete “2)” after 18-090 and add “Table 18”.
Status: Implemented

Date: 10/17/2022 12:04:43 PM
Module: 030405l
Version: 24
Page: 35
Comment: Change “4-012 1) and 4-040 1)” in the third paragraph to “12-402 1) and 12-406 1)”.
Status: Implemented

Date: 11/23/2023 12:29:16 PM
Module: 030405l
Version: 25
Page: 34
Comment: Top of page - Read Rule 22-102 Type of construction to be replaced as Read Rule 22-102 Electrical equipment
Status: Approved for Review

Date: 11/23/2023 12:24:57 PM
Module: 030405l
Version: 25
Page: 17
Comment: Last paragraph referring to Rule 18-150(2c) to be removed because it is no longer referred to in Canadian Electrical Code
Status: Approved for Review

Date: 11/23/2023 12:22:01 PM
Module: 030405l
Version: 25
Page: 8
Comment: Top of page - Should say "Read Rule 18-074 Bonding in Hazardous locations." - First bullet - should refer to Rule 10-616 not 10-614
Status: Approved for Review

Date: 11/23/2023 12:16:38 PM
Module: 030405l
Version: 25
Page: 7
Comment: Third paragraph - Should be referring to Rules 18-064, 18-066 and 18-070
Status: Approved for Review

Date: 11/23/2023 12:13:34 PM
Module: 030405l
Version: 25
Page: 7
Comment: Second paragraph, fourth sentence should refer to Table B18-3 not Table B18-2
Status: Approved for Review

Date: 11/22/2022 10:17:53 AM
Module: 030405m
Version: 24
Page: 17
Comment: The feedback for Question 4 of the Objective 4 Activity Answers should say “Rule 24-304 5)”.
Status: Implemented

Date: 12/5/2022 9:28:03 AM
Module: 030405o
Version: 24
Page:
Comment: The ANSI/TIA-568 standard changed from version C to D in 2015. There are FOUR places to make this update in 0304050. Change “ANSI/TIA 568-C.2” in the second paragraph of page 37 to “ANSI/TIA-568-D”. Change “ANSI/TIA-568-C” in the third paragraph of page 39 to “ANSI/TIA-568-D”. Change “ANSI/TIA 568-C” in questions 2 and 4 on page 42 to “ANSI/TIA-568-D”.
Status: Implemented

Date: 12/6/2023 11:43:45 AM
Module: 030405o
Version: 25
Page: 6, 11
Comment: page 6 the second last paragraph on the page suggests using a 40 11/16" x 2 1/8" box, should be 4 11/16" page 11 the calculation for the circuit ampere rating is shown as 18.125 / 0.5 = 22.656, it should read 18.125 / 0.8 = 22.656 (0.8 is the correct factor for sizing continuous loads)
Status: Approved for Review


Archived Comments

Year: 2021

12/14/2021 1:26:07 PM
Module: 030405o
Version: 21
Page: 44
Comment: Objective Five Exercise Answers: Question 1 needs to be changed to FT6. The FT4 rating is based on the 2015, 23rd Edition of the CEC. See Rule 2-130, Appendix B of the 2018 or 2021 CEC.
Status: Implemented

12/10/2021 10:12:10 AM
Module: 030404g
Version: 21
Page: 35
Comment: The reference to (Rule 10-702) in the first diagram is incorrect and needs to be changed to (Rule10-104). Rule 10-702 deals with equipotential bonding and the diagram is referring to the interconnecting conductor between grounding electrodes which is covered within Rule 10-104.
Status: Implemented

12/10/2021 10:04:32 AM
Module: 030404f
Version: 21
Page: 9
Comment: There are three references to the 2015 CEC. My suggestion is to reference the CEC and omit the year or it will have to be changed every 3 years.
Status: Implemented

12/10/2021 9:21:38 AM
Module: 030405n
Version: 22
Page: 19
Comment: There is just a typo: word is "corona" NOT "coronal".
Status: Implemented

12/8/2021 12:42:10 PM
Module: 030405l
Version: 22
Page: 36
Comment: Objective Four Exercise: Question 5. Wet wells shall be classified as what location? For Zone 2 to be the correct answer, the wet well would have to be provided with adequate continuous positive pressure ventilation. The Rule 22-704 is correct. Sewer gas(hydrogen sulphide- H2S) is not only poisonous but also corrosive and flammable; thus without adequate continuous positive pressure ventilation a wet well could be classified as a Zone 1 or Zone 0 location depending on gas concentrations and how often they are present.
Status: Implemented

2/8/2021 1:04:20 PM
Module: 030405i
Version: 21
Page:
Comment: Objective 5 for this module states “Determine the minimum ampacity of the feeder overcurrent device required for a group of motors”; however, the phrase “minimum ampacity” is used incorrectly here. We are always looking for the maximum overcurrent device, not the minimum. This is stated right in the first sentence of Objective 5. Also, as per Section 0, the term “ampacity” is used for conductors not for equipment such as overcurrent devices. This objective should be reworded as “Determine the rating of the feeder overcurrent device required for a group of motors”. This wording matches well with the wording of Objective 3 in the same module.
Status: Declined

2/8/2021 12:59:01 PM
Module: 030405a
Version: 21
Page: 1
Comment: The outcome for 030405a is to "Determine the size of conductors and conduit"; however, conduit sizing was moved to module 030405c during the last outline revision. Reword this outcome to state "Determine the size of conductors.
Status: Declined

Year: 2020

4/17/2020 10:26:27 AM
Module: 030401c
Version: 21
Page:
Comment: The differential compound motor is noted as a motor used when a "nearly constant speed" is required. This is only true when operating at near full load, from no load to full load the overall speed regulation of a shunt motor is better than a differential compound but the speed curve of the differential is almost perfectly flat at near full load. I think this is confusing to students and could be explained better. Adding the differential compound motors speed curve to figure 37 and the torque curve to figure 38 would also be helpful.
Status: Declined

2/24/2020 8:08:51 AM
Module: 030401e
Version: 21
Page: 18
Comment: The answer to question four is incorrect. Although this is how it is explained throughout this module it is fundamentally way off. If context is need please see Electrical Machines, Drives, and Power Systems text by Theodore Wildi, page 382.
Status: Declined

2/12/2020 9:46:44 AM
Module: 030405b
Version: 21
Page:
Comment: 030405b Grounding and Bonding and Distribution Layout – Section 10 • Objective 1, p. 2 – Figure 1 delete Circuit from picture Circuit grounding. Leave in just Grounding. • Objective 1, p.12 – The second bullet point should read “connect the grounded conductor…” • Objective 1, Figure 13 – Cross-out “Bonding Screw Installed” text in top left of diagram.
Status: Implemented

2/12/2020 9:44:39 AM
Module: 030405a
Version: 21
Page:
Comment: 030405a Conductors – Section 4 • Objective 1, Figure 2 – Should say “Ampacity = Table 1 Value…” (145 A is correct). • Objective 1, Example #3 (p.6, 7) –Add to picture for Panel board to wall greater than 1.2m. Also add from JB to wall greater than 1.2 m. • Objective 1, Example #4 (p.7) – Add to question 1.2 meters from panelboard to area and 1.2 meters at least from area to equipment. Or Change the question to below (from RW 90 conductor) TW 75 wire and Solution should indicate that the ampacity is reduced from the 75o degree column of Table 5A according to insulation: 80 A ÷ 0.75 = 106.6 A. Select a conductor from the 75o degree column of Table 2. A No. 2 AWG would be selected: 115 A x 0.75 = 86.2 A. A No 2 AWG with an allowable ampacity of 86.2 is acceptable for the 80 A load. • Objective 1 Exercise, Q.3 – Add 1.2 meters out of ambient area on either end of the conductor or Change questions to Conductor to (from RW 90) TW 75 Then change answer to #3 AWG. • Objective 2, Example (p. 14) Add based on service OC before Table 16 at bottom of page 14 • Objective 3, (p. 18) 4th line down add underline portion 4-008 1) c) 2) and 4-008 Appendix B • Objective 3 Title for Figure 9 should be changed to underline Figure 9 – Flow chart based on Rules 4-004, 4-006, 4-008 1) 2), and 4-008 Appendix B and Appendix D. • Objective 4, (p.21) Third paragraph down after Voltage Drop. Change last sentence to underlined. Table D4 is handy when applying Rule 46-306 for the remote lamps of unit equipment. • Objective 4, Example #2 (p.22) – Assume all equipment has 90o ratings. • Objective 4, Example #3 (p.24) – A #1 AWG has an allowable ampacity of 130 A at 75o.
Status: Implemented

2/5/2020 11:48:55 AM
Module: 030405h
Version: 21
Page: 7
Comment: In the heading for row housing.....it should refer to 8-200 2) not 8-202 2)
Status: Implemented

2/5/2020 11:46:00 AM
Module: 030405h
Version: 21
Page: 5
Comment: On page , for step 8 add information. Add rule 4-004 22) appendix B and include information that in order to use Table 39 ...markings and labels are required on the equipment to allow you to use Table 39. If no labels must use 14-104 and table 13 and table 2.
Status: Declined

Year: 2019

12/2/2019 2:08:29 PM
Module: 030405e
Version: 21
Page: 40
Comment: The answer to Question 1 should be FT6, not FT4. According to 2-130 Appendix B, FT4 rated conductor is suitable for combustible and non-combustible buildings. FT6 is also rated for the above-mentioned construction and may be used in a plenum as the question mentions. Consider supplying code rule and reference to the appendix as feedback for the question.
Status: Declined

11/12/2019 9:25:55 AM
Module: 030405n
Version: 21
Page:
Comment: Objective 5 has many formatting errors.
Status: Implemented

11/12/2019 9:00:15 AM
Module: 030405n
Version: 21
Page: 12
Comment: When listing the two types of insulation shielding, bullet 1 "Non-metallic insulating shielding" is italicized while bullet 2 is not. Make consistent.
Status: Implemented

10/22/2019 10:24:28 AM
Module: 030405g
Version: 21
Page: 19
Comment: The code rule in the second paragraph needs to be changed from 8-104 5) a) to 8-104 6) a)
Status: Implemented

10/11/2019 3:11:31 PM
Module: 030405h
Version: 21
Page: 21
Comment: For the service calculation, everything is correct with the calculations. The issue is we should be saying T-4 and T-39 both use a 4/0awg with a 200A service. By just mentioning T-4 you may assume T-39 is not considered. If I’m incorrect in my interpretation please get back to me.
Status: Declined

1/1/2019 12:00:00 AM
Module: 030405a
Version: 12
Page: 24
Comment: Would you please check on the DCF (Table D3) formula and add clarification to the ILM as to whether you use the rated conductor temperature or the Conductor allowable ampacity, based on termination temperature. The Masters course offered by NAIT uses Termination Temperature to determine the conductor ampacity and this makes sense based on rule 4-006. Our ILM uses the 90 deg ampacity based on Table 2, yet gives termination temperature of 75 deg 0
Status: Implemented

1/1/2019 12:00:00 AM
Module: 030405g
Version: 12
Page: 5
Comment: First paragraph line five states subrule (2) subrule(3) should be subrule (3) subrule(4)
Status: Implemented

1/1/2019 12:00:00 AM
Module: 030405d
Version: 12
Page: 4
Comment: first sentance of page 4 reads If a conductor is 3m or less and fulfills the requirements of Rule 14-100(c), it may be smaller than required by Rule 14-100(b) and still be acceptable. if we are going to make a statement like this an example would have to be provided to back this up as this is a very unlikely event and may cause confusion for student
Status: Declined

1/1/2019 12:00:00 AM
Module: 030405g
Version: 12
Page: 16
Comment: second paragraph line 2 states a no. 10AWG 90C conductors has an allowable ampacity of 35 A A No 10 AWG from the 75 degree colomn has an allowable ampacity of 35A from the 90 degree colomn the allowable ampacity is 40A Suggest changing too- from the 75 degree colomn the allowable ampacity for the No. !0 AWG 90 degree would be 35A
Status: Implemented

1/1/2019 12:00:00 AM
Module: 030405i
Version: 14
Page: 24
Comment: 3rd paragraph If locked rotor current is not listed on the equipment nameplate, it is assumed to be six times the full load current rating. (we do not have to assume cec gives us a value to use) should read If locked rotor current is not listed on the equipment Refer to Rule 28-010 Locked rotor current rating where not marked, deemed to be equal to six times the FLA rating from the nameplate
Status: Implemented

1/1/2019 12:00:00 AM
Module: 030405l
Version: 12
Page: 20
Comment: Question 5, obj. 2 The term 'may be' denotes permission to do something. The given answer is False for this question. It should be True. You may install equipment approved for Class1, Div 1 locations in a Zone 0. The question does not state any requirements. So, as long as specific requirements are met, YOU MAY INSTALL class1 div 1 equipment in zone 0
Status: Implemented