Refrigeration and Air Conditioning Mechanic (RAC)

Fourth Period Package (26 Modules) Comments

There are no comments to view for this package. Leave a comment »


Archived Comments

Year: 2022

1/31/2022 3:10:44 PM
Module: 140401b
Version: 21
Page: 11
Comment: To clarify the refrigerant flow through the system, the diagram should be updated to show that not only R-14 exists in the First Stage Separator, but also, R-508B also exists at this point.
Status: Implemented

Year: 2021

11/29/2021 4:07:34 PM
Module: 140401dA
Version: 21
Page: 29
Comment: 1. Diagram arrow for Compressor Discharge is pointing in the wrong direction. Should point to the left. 2. Diagram arrow on line above the Controller pressure receiver, to the far left should be pointing down, not up. 3. Three way valve above dump trap is drawn as a two way valve. 4. Box with two fans on the upper left of the diagram should be labelled "Condenser" to be consistent with other drawings in ILM.
Status: Implemented

Year: 2020

11/18/2020 10:07:39 AM
Module: 140401f
Version: 21
Page: 21
Comment: question 7 for the self test seems to be wrong answer should be false. valves are not allowed in between pressure vessel and relief device. ( referencing pg 12) clause B.2.4. thanks for your time
Status: Declined